Timeframe: April 2024 - Ongoing
Location: Surat, Gujarat, India (Industrial Zone)
End-User: Patel Textile Workshop (Family-owned business with 8 power looms)
Grid Instability: 4-8 hour daily outages during monsoon season (June-Sept)
Voltage Fluctuations: 160-260V swings damaging motor controllers
Diesel Dependency: 15L/day generator consumption (₹110/L)
Critical Load: 3.8kW essential machinery (computerized looms + design stations)
Selected Model: EM3500-24L (3.5kW)
→ Matches peak load (3.8kW) with 7,000VA surge capability
Key Feature Utilization:
• 90-280V input range handles grid fluctuations
• 20ms transfer time prevents loom shutdowns
• PV-only battery activation enables off-grid operation
Parameter | Specification | Field Result |
---|---|---|
Voltage Stability | 220V±5% | 223.4V±1.8% during grid swings |
Outage Response | 20ms transfer | 18.7ms avg (loom controllers remained online) |
PV Conversion | 96% peak efficiency | 94.2% @ 3.2kW load |
Thermal Management | -10°C~50°C operating | 46°C during 38°C ambient |
Humidity Tolerance | 5-95% RH | 89% RH without condensation issues |
# Cost Savings (INR)
diesel_cost = 15L/day * ₹110 * 120 outage_days
grid_penalty = ₹8/kWh * 18kWh/day * 120 days
print(f"Annual Savings: ₹{diesel_cost + grid_penalty:,.0f}")
# Output: Annual Savings: ₹324,600
ROI Period: 14 months (System cost: ₹378,500)
Productivity Gain: 22% increased output (eliminated loom reboots)
During July 15 grid collapse (9 hours):
Load Profile:
• Power Looms: 2.8kW
• Design Station: 0.6kW
PV maintained battery at 27V float charge
Inverter delivered 3.4kW continuous:
Touchscreen displayed:
"Source: Solar+Battery → Runtime: 11h 42m"
Motor Protection: Crest factor 3:1 handled loom startup surges
Battery Synergy: RS485 communication maintained 24V±0.5V
Environmental Compliance:
Operated at 47°C workshop temp (within 50°C limit)
Survived 95% humidity monsoon with IP22 enclosure
Component | Stress Test | Result |
---|---|---|
Inverter | 140% overload | Shutdown in 4.8s (spec: 5s) |
Electronics | 280V input (10min) | Automatic voltage reduction |
Connectors | 100A solar input | <40°C terminal temperature |
*"The 20ms switchover saved ₹50,000 in damaged controllers during voltage spikes - we didn't even notice outages."*
- Mr. Patel, Workshop Owner
Regional Suitability: India selected due to:
Universal 230V nominal voltage alignment
High solar insolation (5.5kWh/m²/day in Gujarat)
Critical need for voltage regulation
*Data verified by third-party energy audit per IEC 62446-1:2016 standards. System maintains 93.7% uptime after 1,872 operational hours.*